9
Position
Table b curve
speed
DIP switch position
Air output
Pressure
Power
consumption
Setting Qv Pf Pe
(Number) 1 2 3 4 5 6 7 [m
3
/h] [Pa] [W]
Absent 0 - - - - - - - 58 3 2
Low 1b Off - - - - - On 83 9 4
Low 2b On - - - - - On 138 14 5
Medium 3b - Off Off - - - On 165 20 6
Medium 4b - On Off - - - On 215 34 10
Medium 5b - Off On - - - On 271 53 16
Medium 6b - On On - - - On 324 77 25
High 7b - - - Off Off Off On 298 65 29
High 8b - - - On Off Off On 353 92 31
High 9b - - - Off On Off On 381 107 38
High 10b - - - On On Off On 405 121 45
High 11b - - - Off Off On On 428 134 52
High 12b - - - On Off On On 452 149 60
High 13b - - - Off On On On 475 163 69
High 14b - - - On On On On 502 184 82
Table B - Table A or B is selected by setting DIP switch 7 to on or off.