EasyManuals Logo

Orion Control Systems AAON VCCX2 User Manual

Orion Control Systems AAON VCCX2
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
57
VCCX2 Controller Technical Guide
RSMZ Inputs Wiring
The RSMZ monitors and controls one refrigeration circuit of
the HVAC unit. The RSMZ is used on RZ units and on RN-E
units with Danfoss compressors. The module is designed for
R410-A refrigerant.
The RSMZ is connected to the VCCX2 Controller. Three or six
RSMZ Modules can be connected, depending on the size of the
system. There are two E-BUS Expansion Ports which allow the
use of communicating sensors and E-BUS modules. There is a
MODBUS terminal block which allows wiring to the Reheat
Expansion Module or VFD Compressor.
The RSMZ must be connected to an 18-30 VAC power source.
When wiring the RSMZ Controller, its relay outputs must be
wired as wet contacts (connected to 24 VAC). See Figure 38,
this page for input wiring.
WARNING: Observe Polarity! All boards must be wired
with GND-to-GND and 24 VAC-to-24
VAC. Failure to observe polarity will result
in damage to one or more of the boards.
ALARM
UP
DOWN
ENTERMENU
18-30 VAC
GND
Line Voltage
Size transformer for correct total
load. RSMZ Controller = 18 VA
COM
+
BK
RD
WH
RSMZ
Head Pressure
Transducer
Discharge
Temperature
Sensor
Compressor 1 Status
Compressor 1 Status
Oil Level Switch
Condenser Fan
Figure 38: RSMZ Inputs Wiring
WIRING
RSMZ Inputs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Orion Control Systems AAON VCCX2 and is the answer not in the manual?

Orion Control Systems AAON VCCX2 Specifications

General IconGeneral
BrandOrion Control Systems
ModelAAON VCCX2
CategoryController
LanguageEnglish

Related product manuals