This pot is factory pre-set to suit ½ HP motors. Should changes be required in the
field, proceed as follows: Monitor the motor current. Turn the current limit RV4
to minimum (full CCW). Stall the motor. Advance the pot slowly until the desired
current is achieved. This should not exceed 125% of the motor nameplate rating.
Do not stall the motor for more than a few seconds, or damage may occur.