Osaka - F 10 - User Manual - V1 - PAG. 10
7. PROBLEMS, MAINTENANCE AND WARRANTY
7.1 Notifications
7.1.1 Error messages
Error Reason Action
E1 -E1
E2 -E2
The probe may be interrupted
(
E) or in short circuit (-E) or may
measure a value outside the
range allowed
Check the probe connec-
tion with the instrument
and check that the probe
works correctly
epr
Internal EEPROM memory error Press
set
key
err
Fatal memory error
Replace the instrument or
ship to factory for repair
7.1.2 Other messages
Message Reason
od
Delay at power-on in progress
Ln
Keyboard locked
Hi
Maximum temperature alarm in progress
Lo
Minimum temperature alarm in progress
AL
Digital Input alarm in progress
oP
Door Open
dEF
Defrost in progress with d.dL = Lb
PdF
Post-defrosting in progress with d.dL = Lb
Eco
Eco Mode in progress
7.2 Cleaning
We recommend cleaning of the instrument only with a slightly
wet cloth using water and not abrasive cleaners or solvents.
7.3 Warranty and Repairs
This device has a guarantee in form of repair or replacement by
manufacturing defects in materials of 12 months from the date
of purchase.
OSAKA SOLUTIONS automatically void this guarantee and is not
liable for any damages deriving from:
• Use, installation, or use and handling undue, others than
those described above and, in particular, differs from the
safety requirements established by the regulations.
• Use in applications, machines or electrical panels that do not
provide adequate protection against liquids, dust, grease and
electric shocks to the installation conditions made.
• The inexperienced handling, and / or alteration of the product.
• The installation / use in applications, machines or electrical
panels do not comply with the valid norm.
In case of defective product under warranty or out of that period,
it should contact the post sales service to perform the necessary
steps. Request document repair “RMA” (by mail or fax) and complete
it, is necessary send the RMA and the device to SAT OSAKA by
method prepaid.
7.4 Disposal
The appliance (or the product) must be
disposed of separately in compliance
with the local standards in force on
waste disposal.
8. TECHNICAL DATA
8.1 Electrical characteristics
Power supply: 230 VAC, 115 VAC, 12 VAC/VDC ±10%;
AC frequency: 50/60 Hz;
Power consumption: about 3 VA;
Inputs: 2 inputs for temperature probes:
NTC (103AT-2, 10 kΩ @ 25°C);
1 free of voltage digital input as an alternative
to input Pr2;
Output: 1 relay output SPST-NO:
EN 61810 EN 60730 UL 60730
Out1 (H) - SPST-NO - 30A -
2HP 250V,
1HP 125 VAC
30 (15) A 15 (15) A 15 A Res.,
96 LRA,
16 FLA
Out1 (R) - SPST-NO - 16A -
1HP 250V,
1/2HP 125 VAC
16 (9) A 10 (4) A 12 A Res.,
30 LRA,
5 FLA
12 A max. for those with removable terminal model;
Relay output Electrical life: 100000 operations;
Action type: Type 1.B (EN 60730-1);
Overvoltage category: II;
Protection class: Class II;
Isolation: Reinforced insulation between the low voltage parts
(type C or D power supply and relay output) and front panel;
Reinforced insulation between the low voltage parts (type C
or D power supply and relay output) and the extra low voltage
section (inputs), No insulation between type F power supply and
inputs.
8.2 Mechanical characteristics
Housing: Self-extinguishing plastic, UL 94 V0;
Heat and fire resistance category: D;
Ball Pressure Test as described in EN60730: accessible parts
75°C; support live parts 125°C;
Dimensions: 78 x 35 mm, depth 64 mm;
Weight: about 150 g;
Mounting: Incorporated flush in panel (thickness max. 12 mm)
in
a 71 x 29 mm hole;
Connections:
Inputs: fixed or removable screw terminal block for
0.2 ÷ 2.5 mm
2
/AWG 24 ÷ 14 cables;
Power supply and Outputs: fixed or removable screw ter-
minal block or Faston 6.3 mm for 0.2 ÷ 2.5 mm
2
/
AWG 24 ÷ 14 cables;
Protection degree: IP65 (NEMA 3S) mounted with gasket;
Pollution degree: 2;
Operating temperature: 0 ÷ 50°C;
Operating humidity: < 95 RH% with no condensation;