EasyManua.ls Logo

Oval EL0122 - About Alarm Output (Option)

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-122-8-E
1
7.5.5 About Alarm Output (option)
When the instantaneous flowrate exceeds (or falls below) a preselected setpoint, the counter lights up a
front-panel LED and, at the same time, produces a remote alarm output (non-contact relay).
Alarm comes in Alarm 1 and Alarm 2 which can independently be established.
For parameter menu trees associated with alarms, see "Table 7.5 Menu Trees and Switch
Operation" on page 19.
Parameter Symbol Name Description
A 1 d □□□□□
Alarm 1 setup Sets flowrate at alarm output 1 (in hourly flowrate).
A 1 H □□□□□
Alarm 1 hysteresis
Hysteresis at alarm output 1 (set in hourly flowrate)
 … the width or lag from alarm setpoint to alarm cancellation
A 1 S    △○
Alarm 1 status
Alarm 1 output status
: High alarm or low alarm setup
"H" set high alarm
"L" set low alarm
: Remote output at an alarm (non-contact relay)
"S" set shorted ( contacts "closed")
"O" set open  ( contacts "open")
A 2 d □□□□□
Alarm 2 setup Alarm output 2 flowrate (similar to A1S in meaning)
A 2 H □□□□□
Alarm 2 hysteresis Alarm output 2 hysteresis (similar to A1S in meaning)
A 2 S    △○
Alarm 2 status Output status of alarm output 2 (similar to A1S in meaning)
Example: A1d=500, A1H=5, A1S=LS, A2d=1000, A2H=10, A2S=H0
OFF ON
Instant. flowrate
Alarm 1 LED
A2d=1000
A2H=10
A1H=5
A1d=500
O: Open C: Closed
Alarm output 1
Alarm 2 LED
Alarm output 2
C
C CO
O O
OFF
OFFOFF
ON
Table 7.3 Parameters Associated with Alarm Functions and their Meanings