SECTION 2 SPECIFICATIONS
10
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 160-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 160-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 208 VAC ∆ ±10%, 47-63 Hz 28 A
rms
40 A
2) 220 VAC ∆ ±10%, 47-63 Hz 26 A
rms
40 A
3) 230 VAC ∆ ±10%, 47-63 Hz 25 A
rms
40 A
4) 240 VAC ∆ ±10%, 47-63 Hz 25 A
rms
40 A
5) 220/380 VAC ±10%, 47-63 Hz 15 A
rms
20 A
6) 230/400 VAC ±10%, 47-63 Hz 14 A
rms
20 A
7) 240/416 VAC ±10%, 47-63 Hz 14 A
rms
20 A
( cost option )
8) 277/480 VAC ±10%, 47-63 Hz 14 A
rms
20 A
MODEL 305-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 305-AMX single phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 100 VAC ±10%, 47-63 Hz 12 A
rms
25 A
2) 110 VAC ±10%, 47-63 Hz 12 A
rms
25 A
3) 120 VAC ±10%, 47-63 Hz 11 A
rms
25 A
4) 200 VAC ±10%, 47-63 Hz 7 A
rms
15 A
5) 208 VAC ±10%, 47-63 Hz 7 A
rms
15 A
6) 220 VAC ±10%, 47-63 Hz 6 A
rms
15 A
7) 230 VAC ±10%, 47-63 Hz 6 A
rms
15 A
8) 240 VAC ±10%, 47-63 Hz 5 A
rms
15 A