SECTION 2 SPECIFICATIONS
14
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 3120-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 3120-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 208 VAC ∆ ±10%, 47-63 Hz 58 A
rms
80 A
2) 220 VAC ∆ ±10%, 47-63 Hz 54 A
rms
80 A
3) 230 VAC ∆ ±10%, 47-63 Hz 52 A
rms
80 A
4) 240 VAC ∆ ±10%, 47-63 Hz 50 A
rms
80 A
5) 220/380 VAC ±10%, 47-63 Hz 32 A
rms
40 A
6) 230/400 VAC ±10%, 47-63 Hz 30 A
rms
40 A
7) 240/416 VAC ±10%, 47-63 Hz 30 A
rms
40 A
( cost option )
8) 277/480 VAC ±10%, 47-63 Hz 28 A
rms
40 A