188 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Installation
6
8.  Mount the cabinet top part back on the cabinet bottom part by rst placing the top part with 
the two upper claws (16) on the bottom part and then pressing the bottom edge of the top 
part carefully against the bottom part, until the two bottom claws (17) latch.
9.  For mono-bloc systems: Wall mounting is now concluded. 
For bi-bloc system: Replace the cover of the detached remote controller (20) in the front 
panel (18) of the indoor unit by the cover for the remote controller opening (21), supplied 
within the scope of delivery, to seal the opening (19). Exercise caution as you press the 
cover, until the six latching hooks (22) engage on the front panel.
F G
UP
16
17
18
19
20
21
22
  F  Mounting top/ bottom part
 16  Top  claws
 17  Bottom  claws
  G  Front panel indoor unit
 18  Front panel of the indoor unit
 19  Remote controller opening
 20  Removing the cover of the dismounted remote controller
 21  Inserting the cover for the remote controller opening
 22  Latching hooks (total 6)
6.9  Starting up the system
Commissioning of the system covers the evacuation of the refrigerant circuit (only for bi-bloc 
systems), lling the water system, the concluding inspection of the system installation, test run as 
well as system handover and instruction of the customer.
6.9.1  Evacuating the refrigerant circuit and carrying out a pressure test
 
 Note
In the case of mono-bloc systems, you can skip this section. Continue with section → 6.9.2.2 Filling 
the heating or cooling circuit, p. 191.