Installation Information
Attached accessories
Accessories: Flaring piping kit
CZ-4F5, 7, 10AN (A181K)
CZ-52F5, 7, 10AN (A241K)
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
• Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3 m.
• If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
• Do not place any obstacles which may cause a short circuit of the discharged air.
• If piping length is over 10m, additional refrigerant should be added as shown in the table.
No.
1
2
3
4
5
Accessories part
Installation plate
Installation plate fixing screw
Vinyl tape
Vinyl tape
Band
INDOOR UNIT
OUTDOOR UNIT
Qty.
1
6
3
1
2
No.
6
7
8
9
Qty.
1
2
2
1
MODEL
A181K
A241K
Piping size
Gas
1/2"
5/8"
Liquid
1/4"
1/4"
Rated
If the unit will be installed at a 12m distance, the quantity of additional refrigerant should be
60g…(12–10)m × 30g/m = 60g (Example : A241K)
Max.
Piping
Length
A (m)
25
25
Max.
Elevation
B (m)
20
20
Length
(m)
7.5
7.5
Elevation
(m)
5
5
Additional
Refrigerant
(g/m)
20
30
Piping length and the elevation.
SELECT THE BEST LOCATION
Accessories part
Remote control
Battery
Air purifiying filter
Drain elbow