30
12.5. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.5.1. Fan Speed Rotation Chart
12.5.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi, Me and Lo-.
- Deodorizing Control will be activated.
Speed
CS-A24JKD CS-A18JKD
Cool, Dry Heat
S Hi Hi 1660 1440
Hi 1570 1400
Me Me 1480 1320
Lo+ Lo 1380 1270
Lo 1280 1190
Lo- Lo- 1070 980
S Lo S Lo 830 760
SS Lo 300 300
Q SHi Q Hi 1560 1340
Q Hi 1470 1300
Q Me Q Me 1380 1220
Q Lo 1280 1170
Q Lo 1180 1090