13.20  Compressor Reverse Rotation Protection Control 
•  If the compressor is operating continuously for 5 minutes or longer and the temperature difference between 
intake air and indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart 
automatically. 
•  Time Delay Safety Control is activated before the compressor restart. 
 
 
 
s T = Intake air temperature - Indoor heat exchanger temperature 
•  This is to prevent compressor from rotate reversely when there is an instantaneous power failure. 
 
13.21  Dew Prevention Control 
•  To prevent dew formation at indoor unit discharge area. 
•  This control starts if: 
o  Cooling mode or Quiet mode is activated. 
o  Remote Control setting temperature is less than 25°C. 
o  Fan speed is at Lo or QLo. 
o  Room temperature is constant (±1°C) for 30 minutes. 
o  Compressor is continuously running. 
•  Fan speed, angle of horizontal louver (vertical airflow angle) and angle of vertical louver (horizontal airflow angle) 
will be adjusted accordingly in this control.  
o  Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed. 
o  The angle of horizontal louver will be changed as table below: 
o  The angle of vertical louver will be changed as table below: 
•  Dew prevention stop condition 
o  Remote control setting temperature is more than 25°C. 
o  Fan speed is not set to Lo or QLo. 
o  Select Powerful operation. 
 
(For 13.22 to 13.23 information applies only to Heating Operation) 
13.22 Restart Control (Time Delay Safety Control) 
•  When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- 
o  Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. 
•  If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the 
moment operation stop, although the unit is turn on again within the period. 
•  This phenomenon is to balance the pressure inside the refrigerant cycle. 
 
13.23  Compressor Reverse Rotation Protection Control 
•  If the compressor is operating continuously for 5 minutes or longer and the temperature difference between 
indoor heat exchanger and intake air is 5°C or less for continuous 2 minutes, compressor will stop and restart 
automatically. 
•  Time Delay Safety Control is activated before the compressor restart. 
 
 
 
s T = Indoor heat exchanger temperature - Intake air temperature 
•  This is to prevent compressor from rotate reversely when there is an instantaneous power failure.