This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
The 5 times counter can be reset when either one of the following condition happen:
- Unit is OFF by remote control or AUTO OFF/ON button.
- Indoor intake temperature - Indoor piping temperature > 5°C for 1 minute or more.
- Operation mode change.
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
TIMER LED blinking will be reset if:
- Indoor intake temperature - indoor pipe temperature > 5°C for 1 minute or more
- Power supply reset.
13.7. Dew Prevention control
To prevent dew formation at indoor unit discharge area.
This control start if:-
- Cooling mode or Queit mode is activated.
- Remote Control setting temperature is less than 25°C.
- Fan speed is at Lo or QLo.
- Room temperature is constant (±1°C) for 30 minutes.
- Compressor is continuously running.
Fan speed will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
Dew prevention stop condition.
- Remote Control setting temperature is less than 25°C.
- Fan speed is at Lo or QLo.
- Select Powerful operation.