13.15.1.7  Setting Position Judgment 
  According to installation position when there is only one activity area detected, the horizontal airflow direction 
louver position is fixed according to chart below: 
 
Horizontal airflow direction louver position 
Target area 
Left installation  Center installation  Right installation 
A 3 2 2 
B 1 1 1 
C 5 5 4 
  Louver position refer to horizontal airflow direction control. 
 
  When 2 activity areas have been detected, according to Human Activity Level, the timing of horizontal airflow 
direction louver steps at the targeted activity areas is judged. 
 
Operation mode  Activity level difference  Louver stop time 
1 level 
Higher Activity level ≈ 60 seconds 
Lower Activity level ≈ 30 seconds 
Cooling 
2 levels 
Higher Activity level ≈ 60 seconds 
Lower Activity level ≈ 8 seconds 
 
  When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow 
louver steps at the targeted activity areas is judged. 
 
Operation mode  Activity level  Louver stop time 
Cooling 
Hi 
Me 
Lo 
≈ 45 seconds 
≈ 30 seconds 
≈ 20 seconds 
 
  When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right. 
13.15.1.8 Setting Temperature and Fan Speed Shift  
  Cooling Dual Sensor 
 
 
 
*  During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached. 
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.