14.7  Dew Prevention Control 
  To prevent dew formation at indoor unit discharge area. 
  This control starts if: 
o  Cooling mode or Quiet mode is activated. 
o  Remote Control setting temperature is less than 25°C. 
o  Fan speed is at CLo or QLo. 
o  Room temperature is constant (±1°C) for 30 minutes. 
o  Compressor is continuously running. 
  Fan speed will be adjusted accordingly in this control. 
o  Fan sped will be increased slowly if the unit is in quiet mode and Lo fan speed. 
  Dew prevention stop condition. 
o  Remote control setting temperature is more than 25°C. 
o  Fan speed is not at Lo or QLo. 
o  Select Powerful operation.