13.5. Freeze Preventive Control
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more than 4 minutes
and compressor turn off.
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed will be increased
according to the indoor pipe temperature the figure below:
Restart control (Time Delay Safety Control) will be applied in this control if the recovery time is too short.
13.6. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
Time Delay Safety Control is activated before the compressor restart.
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.

Table of Contents

Other manuals for Panasonic CS-C7HKD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-C7HKD and is the answer not in the manual?

Panasonic CS-C7HKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-C7HKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals