12.3 Automatic Operation  
  Automatic operation can be set using remote control. 
  This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature. 
  After judged the temperature, the operation mode is determined by referring to the below standard. 
 
 
 
  Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with 
the setting temperature as shown in table below. 
 
  Setting Temperature (Standard) 
Cooling Operation  25°C 
Soft Dry Operation  22°C 
 
  The setting temperature for all the operations can be changed one level up or one level down from the standard 
temperature as shown in table below by pressing the temperature up or temperature down button at remote 
control. 
 
 Cooling Soft Dry 
Higher  Æ +2°C  27°C  24°C 
Standard  Æ ±0°C  25°C 22°C 
Lower  Æ -2°C  23°C 20°C 
 
  The operation mode judging temperature and standard setting temperature can be increased by 2°C 
permanently, by open the circuit of JX03 at indoor unit’s printed circuit board. 
 
   
 
  Setting Temperature (Standard) 
Cooling Operation 
 
Cooling Operation  27°C 
Intake Air 
Temperature 
 
25°C 
 
Soft Dry Operation 
 
Soft Dry Operation  24°C 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Cooling Operation 
Intake Air 
Temperature 
 
23°C 
 
Soft Dry Operation