9.5. Louver Control
9.5.1. Louver control for cassette type
•
• •
•
When power is on, at the same time, louver start initializing toward to close Direction.
•
• •
•
During operation, stopping, thermostat off condition, louver angle set manual or auto depend on remote controller setting.
−
− −
−
Louver manual setting
Operation mode Display manual
Set 1 Set 2 Set 3 Set 4
Normal 20° 35° 50° 70°
Heating Defrost 10°
Hot start 10°
Thermostat off 20°
Fan 20° 35° 50° 70°
Cooling Normal 20° 35° 50° 70°
(fan) Dew control 50°
Thermostat off 20° 35° 50° 70°
Normal 30°
Dry Dew control 50°
Thermostat off 20° 35° 50° 70°
Operation mode judge 20° 35° 50° 70°
Stop mode 0°
−
− −
−
Louver auto setting
Operation Display auto set
AUTO 1 AUTO 2 AUTO 3
A 70° 70° 70°
Normal Sensor B 20° - 70° 20° - 50° 40° - 70°
Heating C 20° 20° 20°
Defrost 10°
Hot start 10°
Thermostat off 20°
Fan 20° - 70° 20° - 50° 40° - 70°
Cooling Normal 20° - 70° 20° - 50° 40° - 70°
(Fan) Dew control 50°
Thermostat off 20° - 70° 20° - 50° 40° - 70°
Normal 30°
Dry Dew control 50°
Thermostat off 20° - 70° 20° - 50° 40° - 70°
Operation mode judge 20° 20° 20°
Stop mode 0°
•
• •
•
Temperature range for louver control during heating operation is as follows; decide by indoor heat exchanger temperature.
AUTOBW1 AUTOBW2 AUTOBW3 AUTOBW4
60°C 57°C 30°C 25°C