9.6.8. Thermostat Control
Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
If temperature difference matches values shown below, thermostat switches off or on accordingly.
9.7. Protection Control
9.7.1. Outdoor Low-pressure Protection Control
The purpose of low-pressure protection control is gas leakage detection control.
The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
After 6 occasions, suction pressure error is displayed; all operation stopped except outdoor fan remaining heat removal control.
9.7.2. Outdoor High-pressure Protection Control
The high-pressure protection control starts when high-pressure switch is activated less than 15 minutes after compressor
startup.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.3. Discharge Temperature Protection Control
The discharge temperature protection control starts when abnormal compressor temperature 115°C is detected when outdoor
unit is operating in cooling operation.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.4. Over Current Protection Control
The purpose of over current protection control is to protect the air conditioner from over current.
The over current protection control starts when input current from CT is maintained at 20A or more for 2 seconds when the
outdoor unit is starting up or during cooling operation.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 4 occasions, over current protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.5. CT Disconnection Detection Control
CT disconnection detection control detects if the CT sensor works normally.
The CT disconnection detection activates when:
- CT input value is maintained at compressor shutdown status (1.5A or less) consecutively for 2 seconds when the compressor
is operating;
- During this condition, compressor is shut down and indoor unit is set to thermo-off status.
- After 4 occasions, CT sensor error is displayed; all operation stopped except outdoor fan remaining heat removal control.
- CT input value is maintained at compressor operation status (5A or more) consecutively for a period of 60 seconds when the
compressor is shut down.
- During this condition, CT sensor error is displayed.
9.7.6. Connection Capacity Protection Control
The purpose of connection capacity protection control is to ensure the total capacity of connected indoor units is within
acceptable range.
During this protection control, connection capacity error is displayed; all operations stopped.
Thermostat OFF Thermostat ON
Cooling Mode -1.5°C-0.5°C
Soft Dry Mode -2.5°C-2.5°C
Model Number Min. Capacity (kW) Max. Capacity (kW) Model Number Min. Capacity (kW) Max. Capacity (kW)
CU-J14DBE5 5.3 6.9 CU-J28DBE8 6.3 9.8
CU-J18DBE5 5.3 6.9 CU-J34DBE8 7.3 12.3
CU-J24DBE5 5.3 6.9 CU-J43DBE8 10.2 13.8
CU-J28DBE5 6.3 9.8 CU-J50DBE8 12.7 15.8
CU-J34DBE5 7.3 12.3

Table of Contents

Other manuals for Panasonic CS-F50DTE5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F50DTE5 and is the answer not in the manual?

Panasonic CS-F50DTE5 Specifications

General IconGeneral
Indoor unit typeCeiling
Indoor unit weight47000 g
Indoor units quantity1
Indoor unit dimensions (WxDxH)1600 x 700 x 250 mm
Indoor unit noise level (high speed)50 dB
Outdoor unit weight105000 g
Outdoor unit noise level56 dB
Outdoor unit dimensions (WxDxH)900 x 320 x 1340 mm
Hose length (max)50 m
Inverter technologyYes
Refrigerating mediumR410A
Cooling capacity (max)47700 BTU/h
Heating capacity (max)54600 BTU/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)14000 W
Heating capacity in watts (max)16000 W
Cooling energy efficiency (EER, W/W)2.91
Heating energy efficiency (COP, W/W)3.41