87
5. Charging hose
The pressure resistance of the charging hose has been
raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and the
size of the fitting has been changed to match the
manifold ports.
Fig. 4 Manifold gauge charging hose
Table 8 Difference between R410A and conventional charging hoses
6. Vacuum pump adaptor
When using a vacuum pump for R410A, it is necessary
to install an electromagnetic valve to prevent the vacuum
pump oil from flowing back into the charging hose. The
vacuum pump adaptor is installed for that purpose. If the
vacuum pump oil (mineral oil) becomes mixed with
R410A, it will damage the unit.
7. Electric gas leak detector for HFC refrigerant
The leak detector and halide torch that were used with
CFC and HCFC cannot be used with R410A (because
there is no chlorine in the refrigerant).
The present R134a leak detector can be used, but the
detection sensitivity will be lower (setting the sensitivity
for R134a at 1, the level for R410A will drop to 0.6).
For detecting small amounts of gas leakage, use the
electric gas leak detector for HFC refrigerant. (Detection
sensitivity with R410A is about 23 g/year).
Fig. 5 Vacuum pump adaptor
Fig. 6 Electric gas leak detector for HFC refrigerant
Conventional hoses R410A hoses
Pressure
resistance
Working pressure
3.4 MPa (35 kgf/cm
3
) 5.1 MPa (52 kgf/cm
3
)
Bursting pressure
17.2 MPa (175 kgf/cm
3
) 27.4 MPa (280 kgf/cm
3
)
Material NBR rubber HNBR rubber Nylon coating inside

Table of Contents

Other manuals for Panasonic CS-F50DTE5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F50DTE5 and is the answer not in the manual?

Panasonic CS-F50DTE5 Specifications

General IconGeneral
Indoor unit typeCeiling
Indoor unit weight47000 g
Indoor units quantity1
Indoor unit dimensions (WxDxH)1600 x 700 x 250 mm
Indoor unit noise level (high speed)50 dB
Outdoor unit weight105000 g
Outdoor unit noise level56 dB
Outdoor unit dimensions (WxDxH)900 x 320 x 1340 mm
Hose length (max)50 m
Inverter technologyYes
Refrigerating mediumR410A
Cooling capacity (max)47700 BTU/h
Heating capacity (max)54600 BTU/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)14000 W
Heating capacity in watts (max)16000 W
Cooling energy efficiency (EER, W/W)2.91
Heating energy efficiency (COP, W/W)3.41

Related product manuals