– 21 –
MAC9509078C2
CS-G93KE
Operation Details
• When the compressor is in operation, the deodorizing status starts from 1 → 2.
• When the compressor stops operation, the deodorizing status starts from 3 → 4 → 5.
• When the compressor stops operation, indoor fan stops for 330 seconds.
B. Deodorizing Control
• This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
C. Sensible Heat Control
• This control is to improve the feeling in high fan speed and low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition. (During Cooling operation).
Fan Speed
Compressor
ON
ON ON
Deodorizing Status
Compressor
ON
Time (second)
Fan Speed