– 38 –
MAC9509078C2
CS-G93KE
Operation Details
(b) Manual Horizontal vane angle setting
• By pressing the remote control horizontal airflow direction setting switch, the vane will move to the indicated
position (1, 2, 3, 4, 5, 6, 7) as shown in the table.
The purpose of this control is to reduce indoor operating noise. Indoor fan speed is set to Lo- when the following
conditions occur.
• Indoor fan speed is set at Low
• Indoor heat exchanger temperature rises to 17°C or above
• Compressor operates for 5 minutes or more
• Operation frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)
This control is cancelled when one of the following conditions occurs.
• Indoor fan speed is not set at Low
• Indoor heat exchanger temperature is decreased to 13° C or below
• Compressor operation frequency is more than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)
Lo
-
Lo
Indoor Heat
Exchanger Temperature
13°C
17°C
• Horizontal vane angle position
10. QUIET OPERATION
1234567
Operation
Heating
(Left vane position) (Right vane position)
2
125°
125°
110°
125°
110°
125°
3
55°
55°
64°
55°
64°
55°
4
55°
55°
64°
55°
64°
55°
5
55°
55°
64°
55°
64°
55°
6
90°
90°
90°
90°
90°
90°
7
125°
125°
110°
125°
110°
125°
1
90°
90°
90°
90°
90°
90°
2
125°
125°
110°
125°
110°
125°
3
55°
55°
64°
55°
64°
55°
4
125°
125°
110°
125°
110°
125°
5
90°
90°
90°
90°
90°
90°
6
55°
55°
64°
55°
64°
55°
7
55°
55°
64°
55°
64°
55°
1
90°
90°
90°
90°
90°
90°
Anti-dew Formation Control
Anti-dew Formation Control
Fan
Soft
Dry
Cool-
ing
(c) Wide / Spot Airflow Setting
By pressing the remote control WIDE/SPOT switch, the vane will move to position 3 while WIDE and position
2 while SPOT.
WIDE SPOT
32
For All
Operations
Untitled-5 6/20/00, 5:11 PM38