MAC9509078C2
CS-G93KE
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C.
Operation Details
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
+1.5
+1.0
+0.5
0
–0.5
–1.0
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
Less than 38°C
Compressor Operation Frequency (Hz)
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
Less than 38°C
64 (Fc max) or 50
40
31
22
15
15
Comp OFF
38°C and above
92 (Fc max) or 70
49
31
22
16
15
Comp OFF
38°C and above
CS-G93KE CS-G123KE
(ii) When the remote control setting temperature is 24°C and above.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
+1.5
+1.0
+0.5
0
–0.5
–1.0
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
Less than 38°C
Compressor Operation Frequency (Hz)
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
Less than 38°C
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
38°C and above
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
38°C and above
CS-G93KE
• Compressor OFF temperature = Compressor ON temperature.
• The operation frequency can be changed every 30 seconds.
• 30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
• The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and
continues for 3 minutes.
• When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
• When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
• When the compressor stops, the outdoor fan motor stops 30 seconds later.
CS-G123KE
Untitled-3 6/20/00, 5:03 PM18