– 24 –
MAC9509078C2
CS-G93KE
Operation Details
Compressor OFF temperature = compressor ON temperature.
The operation frequency changes every 30 seconds.
When the difference of the intake air temperature and Internal setting temperature is –1.5°C or more, compressor will operate at Fh
continuously for 3 minutes and then change over to Fhmax.
The compressor stops when the intake air temperature reaches 1.5°C above internal setting temperature and continues for 3 minutes.
When the compressor stops, it will not start operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature decreases to the compressor ON temperature, the compressor starts immediately.
When the compressor stops, the outdoor fan motor stops 30 seconds later.
CS-G123KE
+1.5
+1.0
+0.5
0
–0.5
–1.0
–1.5
Heating Operation
Remote Control Setting Temp.
Intake air temperature –
Internal setting temperature
Compressor OFF
Internal setting temp.
Outdoor air temperature
Compressor Operation Frequency (Hz)
Stabilized Period
21°C ~ 30°C
16°C ~ 20°C
Transition Period
16°C ~ 30°C
Comp Off
16
16
22
64
74
86
90 (Fh) or
115 (Fhmax)
Comp Off
16
22
27
36
44
64
90 (Fh) or
115 (Fhmax)
–1°C and
above
Comp Off
16
27
36
44
64
74
90 (Fh) or
115 (Fhmax)
Less than
–1°C
Comp Off
16
22
27
36
44
64
90 (Fh) or
115 (Fhmax)
–1°C and
above
Comp Off
16
22
27
36
44
64
90 (Fh) or
115 (Fhmax)
Less than
–1°C