4.Protection Control
B. Starting Control
Within 300 seconds after the start-up of the compressor, the frequency for the compressor will change as below.
A. Time Delay Safety Control
1. The compressor will not start for 3 minutes after the stop of the operation.
2. This control is not applicable if the power supply is turned off and turned on again.
B. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop for 30 seconds.
2. However, it can be stopped using remote controller or Auto Switch on indoor unit.
C. Total Running Current Control
1. When the total outdoor unit running current(AC) exceeds I1 value, the frequency for compressor will decline.
2. If the running current is less than I1 value for 10 seconds, the frequency for compressor will increase.
3. However, if the total outdoor running current exceeds 17.0A, compressor will be stopped immediately for 3 minutes.