7.8. Delayed ON-Timer Control
Delay ON-Timer can be set using remote controller, the unit with timer set will start operate earlier than the setting timer. This
is to provide a comfortable environment when reaching the set On time.
Seventy minutes before the set time for ON Timer or ON-OFF Timer setting, indoor ( at fan speed of Lo-) and outdoor fan motor
start operate for 20 seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the
operation mode.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Timer Signal Receiving Sound During Operation
Operation Sound Timer LED Timer Setting
ON Timer Set OFF Beep- ON Valid
OFF Timer Set ON Beep- ON Valid
ON-OFF Timer Set OFF Beep- ON Valid
OFF-ON Timer Set ON Beep- ON Valid
Timer Signal Receiving Sound During Operation
Operation Sound Timer LED Timer Setting
ON Timer Set OFF Beep- ON Valid
OFF Timer Set ON Beep- ON Valid
ON-OFF Timer Set OFF Beep- ON Valid
OFF-ON Timer Set ON Beep- ON Valid
7.9. Auto Restart Control
If there is a power failure, operation will be automatically restarted after 3-4 minutes when the power is resumed. It will start with
previous operation mode and airflow direction.
46