B.Angular Speed of Vertical Vane
Vertical Airflow Vane
Airflow Direction Changes or Vertical Airflow Vane Closes 22.06/s
Swings Up and Down (Auto Airflow Direction)
2.21~5.52/s
C. Mode Judgement for Auto Operation
Airflow Mode Setting Auto Manual
Initializing When Power-On Upper Limit Lower Limit
Auto Operation Upper Limit Position Previously Set
Shifted to Auto Mode Same to Cool/Dry/Heat Same to Cool/Dry/Heat
Note:
When the air-conditioner is turned on, if manual airflow direction is selected and the angle is lower than the lower limit
for heating operation, the airflow direction will be changed to the lower limit for heating mode. If Cooling operation is
determined during the mode judgement, the airflow direction will be shifted to lower limit for cooling operation.
D. About Timer-Setting
During On-Timer operation, the airflow direction can be changed between Manual and Auto.