14.4.19 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
Outdoor pipe temperature rise due to defective of outdoor fan motor.
Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting
Is outdoor fan motor operating?
When F95 indication ha
pp
ens
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Check the outdoor unit installation
condition (during cooling or soft-dry
o
p
eration
Replace the outdoor fan motor.
NO
YES
Is there any improper heat radiation?
Replace compressor
Reinstall the outdoor unit
Remove the obstacle(s)
Clean the outdoor heat exchanger
Check the outdoor pipe temperature
sensor.
Does it conform to the sensor
characteristic charts?
Replace outdoor unit PCB
YES
NO
YES
NO