13.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Comp Frequency 45 Hz or above 64 Hz or above 58 Hz or above 73 Hz or above
Total Outdoor Current
1bİ1˘3 1bİ1˘1.6 1bİ1˘1.3 1bİ1˘1.6
Indoor Piping Temp
20 ć or above 25 ć or less 20 ć or above 25 ć or less
Operation Mode Cool/Dry Heat Cool/Dry Heat
Model RE9JKE RE12JKE
13.1.7 Low Operation Frequency Protection Control
If all following conditions exists, the compressor will run with the frequency of 40 Hz (RE9JKE,RE12JKE) or 30Hz
(RE15JKE)
Models RE9JKE, RE12JKE
ıİ˘˚RE15JKE
Intake Air Temp.
ı30 ć or ˘15 ć
-------------------
ı30 ć or ˘14 ćı28 ć or ˘14 ć
Outdoor Temp.
ı38 ć or ˘16 ćı24 ć or ˘4 ćı38 ć or ˘13 ćı24 ć or ˘4 ć
Indoor Piping Temp.
˘30 ćı0 ć˘30 ćı0 ć
Operation Mode Cool / Dry Heat Cool/ Dry Heat
13.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4к.
Indoor temperature and outdoor temperature is 30±5к.
Remote Control setting 16к and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5к.
Indoor temperature and outdoor temperature is 20 ± 2к.
Remote control setting 30к and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.2 Protection Control For Cooling and Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
RE9JKE, RE12JKE RE15JKE
Outdoor air tem