12.15   Odor Cut Control 
•  To reduce the odor released from the unit. 
o Start Condition 
  AUTO FAN Speed is selected during COOL or DRY operation. 
  During freeze prevention control and timer preliminary operation, this control is not applicable. 
o Control content 
  Depends on compressor conditions: 
1. Compressor OFF  Compressor ON. 
 The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds. 
2. Compressor ON  Compressor OFF. 
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.