8.4.3. 7 Minutes Time Save Control
  • The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
  • This phenomenon is to reduce the built up humidity inside a room.
8.4.4. Anti-Freezing Control
  • If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
  • This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
  • Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
  • Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
8.4.5. Compressor Reverse Rotation Protection Control
  • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (cooling mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
  • Time Delay Safety Control is activated before the compressor restart.
▲ T = Intake air temperature - Indoor heat exchanger temperature
  • This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
8.4.6. Starting Current Control
  • When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
  • The reason of the difference is to reduce the starting current flow.