Cooling Operation Time Diagram
Quiet Operation Control
(For Cooling Mode or cooling region of Soft Dry Mode)
Purpose of this operation is to provide quite cooling operation compare to normal operation.
When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
3 dB, against the present sound level operation.
Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
Dew formation become severe at Quiet Lo cool, therefore:
i) For Transistor Motor
Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+100). After that, it goes back to QLo+180 rpm. (However
quiet LED remains on).
ii) For Induction Motor
Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+80). After that, it goes back to QLo+170 rpm. (However quiet
LED remains on).
18
CS-W18CKE CU-W18CKE / CS-W24CKE CU-W24CKE