How to use electronic circuit diagram
TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 42 sec.
Anti-Freezing 4 min. 0 sec.
Auto Mode Judgement 25 sec. 0 sec.
Soft Dry OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Deodorizing Control
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
20 sec. 2 sec.
180 sec. 18 sec.
Soft Dry 40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min. 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Powerful Mode Operation 15 min. 15 sec.
Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.
4 Way Valve 5 min. 30 sec.
After Deice Ended 30 sec. 3 sec. Comp. OFF after deice
Hotstart Delay Times 4 min. 0 sec.
Hotstart Finish Times 2 min. 0 sec.
Ion OFF Timer 30 min. 180 sec.
Ion ON Timer 10 sec. 1 sec.
Quiet Operation Times 1 hr. 30 min. 9 sec.