17.3. Sensible Capacity Chart
Condition
Indoor temperature : 27qC / 19qC
Outdoor temperature : 35qC / 24qC
CS-XE9EKE CU-XE9EKE
CS-XE12EKE CU-XE12EKE
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
230V - 240V Outdoor Temperature (qC)
Indoor wet bulb
temperature
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0qC 2.58 1.96 0.52 2.41 1.88 0.56 2.24 1.80 0.60 2.04 1.71 0.65
19.0qC2.600.57
19.5qC 2.83 2.05 0.53 2.65 1.97 0.57 2.46 1.89 0.61 2.24 1.80 0.66
22.0qC 3.09 2.12 0.54 2.88 2.04 0.58 2.68 1.97 0.62 2.44 1.88 0.67
230V - 240V Outdoor Temperature (qC)
Indoor wet bulb
temperature
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0qC 3.47 2.63 0.81 3.24 2.52 0.87 3.02 2.43 0.93 2.74 2.30 1.00
19.0qC3.500.88
19.5qC 3.81 2.76 0.82 3.56 2.65 0.88 3.31 2.55 0.95 3.01 2.43 1.02
22.0qC 4.15 2.86 0.84 3.88 2.75 0.90 3.61 2.65 0.96 3.28 2.53 1.04