81
Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below
and the positions of the vane are as Figure 2 above.
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 60 75 105 120
* The vertical vane angle tolerance is within +/- 5 degree.
14.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
Purpose
o To provide quiet cooling operation compare to normal operation.
Control condition
o Quiet operation start condition
When “FAN SPEED/QUIET” button at remote control is pressed continuously until QUIET will be shown
on remote control display.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL button is pressed.
Stop by OFF/ON switch.
Timer “off” activates.
When FAN SPEED/QUIET button is pressed again and fan speed is change to Low.
Sleep mode timer delay OFF.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is memorized.
Control contents
o Fan speed is changed to QLo.
14.6 Quiet Operation (Heating)
Purpose
o To provide quiet heating operation compare to normal operation.
Control condition
o Quiet operation start condition
When “FAN SPEED/QUIET” button at remote control is pressed continuously until QUIET will be shown
on remote control display.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL button is pressed.
Stop by OFF/ON switch.
Timer “off” activates.
When FAN SPEED/QUIET button is pressed again and fan speed is change to Low.
Sleep mode timer delay OFF.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is memorized.
Control contents
o Fan speed is changed to QLo.