EasyManuals Logo

Panasonic CS-Z25TKR Service Manual

Panasonic CS-Z25TKR
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
130
17.4.13 H33 (Unspecified Voltage between Indoor and Outdoor)
Malfunction Decision Conditions
The supply power is detected for its requirement by the indoor/outdoor transmission.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit and outdoor unit PCBs used.
Indoor unit or outdoor unit PCB defective.
Troubleshooting
When abnormality indication starts again.
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
Check indoor and outdoor units model number.
Check indoor and outdoor PCB part number and compare if
they matched the part list.
NO
NO
Is the indoor and outdoor unit model number matched?
Match the compatible model (follow specification).
YES
Replace the indoor and outdoor unit PCB.
Change for the specified indoor or outdoor unit PCB.

Table of Contents

Other manuals for Panasonic CS-Z25TKR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-Z25TKR and is the answer not in the manual?

Panasonic CS-Z25TKR Specifications

General IconGeneral
BrandPanasonic
ModelCS-Z25TKR
CategoryAir Conditioner
LanguageEnglish

Related product manuals