170
20. Service Data
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
20.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
- Indoor room temperature: 27°C DryBulb/19°C Wet Bulb
- Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
- Compressor frequency: Rated for cooling operation
- Piping length: 5m
- Voltage: 230/240V
20.1.1 CS-Z20VKR CU-Z20VKR
230V 240V
5 0.830 0.780
16 1.290 1.240
25 1.620 1.570
35 2.000 1.950
46 2.460 2.410
5 1.016 147.358
16 1.082 156.931
25 1.105 160.267
35 1.152 167.084
46 1.337 193.916
5
16
25
35
46
Outdoor
Temperature (°C)
Current (A)
14.800
15.380
16.280
Outdoor
Temperature (°C)
Outdoor
Temperature (°C)
Indoor Discharge
Air Temperature (°C)
14.250
Lo Pressure
(MPa)
19.540
Lo Pressure
(Psi)
0.700
0.900
1.100
1.300
1.500
1.700
1.900
2.100
2.300
2.500
4 6 8 10121416182022242628303234363840424446
Current (A)
Outdoor Temperature (℃)
230V 240V
1.000
1.100
1.200
1.300
1.400
145.000
160.000
175.000
190.000
205.000
4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Lo Pressure (MPa)
Lo Pressure (Psi)
Outdoor Temperature (℃)
230V 240V
14.000
15.000
16.000
17.000
18.000
19.000
20.000
4 6 8 10121416182022242628303234363840424446
Indoor Discharge
Air Temperature (℃)
Outdoor Temperature (℃)
230V 240V