12. Installation Instruction
12.1 Select the Best Location
12.1.1 Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Indoor unit of this air conditioner shall be installed
in a height of at least 1.8 m.
12.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
12.1.3 Indoor/Outdoor Unit Installation
Diagram
Vinyl tape
Remote control holder fi xing screws
6
Remote control holder
5
Remote
control
3
This illustration is for
explanation purposes only.
The indoor unit will actually face a different way.
100 mm
or more
1000 mm
or more
100 mm
or more
300 mm
or more
It is advisable to
avoid more than 2
blockage directions.
For better ventilation
& multiple-outdoor
installation, please
consult authorized
dealer/specialist.
Saddle
Power supply cord
Additional drain hose
Control Board cover
Gas side piping
Connection cable
Vinyl tape (wide)
Apply after carrying
out a drainage test.
To carry out the
drainage test,
remove the air fi lters
and pour water into
the heat exchanger.
Liquid side piping
Piping direction
Attention not to bend
up drain hose
Right
Right
Rear
Right
bottom
Left
Rear
Left bottom
Left
(Front side)
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Attaching the remote control holder to the wall
Insulation of piping connections
( )
( )
( )
( )
( )
( )
(Left and right are identical)
Installation plate
1
Sleeve
Bushing-Sleeve
Bend the pipe as
closely on the wall as
possible, but be careful
that it doesn’t break.
Putty
(Gum Type Sealer)
Installation parts you
should purchase
( )
( )
( )
( )
Flare connection
300 mm
or more
50 mm
or more
65 mm
or more
Table A
Model
Capacity
W
(HP)
Piping size
Std.
Length
(m)
Max
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Piping
Length for
add. gas
(m)
Max.
Refrigerant
Charge
(kg)
Indoor
A
min
(m
2
)
Gas Liquid
Z20*** 3/4HP
9.52 mm
(3/8
")
6.35 mm
(1/4
")
5
15 3 20 10 7.5 0.88 Not applicable (*)
Z25*** 1.0HP 15 3 20 10 7.5 0.98 Not applicable (*)
Z35*** 1.5HP 15 3 20 10 7.5 0.98 Not applicable (*)
Z42*** 1.75HP
12.7 mm
(1/2
")
15 3 30 15 7.5 1.44 Not applicable (*)
Z50*** 2.0HP 15 3 30 15 10 1.47 Not applicable (*)
Z60*** 2.25HP 15 3 30 15 10 1.62 Not applicable (*)
Z71*** 2.5HP
15.88 mm
(5/8
")
20 3 30 25 10 1.82 Not applicable (*)
Z80*** 3.0HP 20 3 30 25 10 1.99 4.80
(*) Systems with total refrigerant charge, m
c
, lower than 1.84kg are not subjected to any room area requirements.
Example: For Z20***
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m × 10 g/m =
25 g.
A
min
= (m
c
/ (2.5 × (LFL)
(5/4)
× h
0
))
2
** not less than safety factor margin
A
min
= Required minimum room area, in m
2
m
c
= Refrigerant charge in appliance, in kg
LFL
= Lower flammability limit (0.307 kg/m
3
)
h
0
= Installation height of the appliance (1.8 m for wall mounted)
SF
= Safety factor with a value of 0.75
** The required minimum room area, A
min
, shall also be governed by the safety factor margin formula below :
A
min
= m
c
/ (SF × LFL × h
0
)
The higher value shall be taken when determining the room area.