Air Circulation Mode Operation Time Diagram
Standard for Determining Operation Mode
8.3. Air Circulation Mode Operation
• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
8.4. Automatic Mode Operation
• Indoor fan operates at SLo fan speed for 25 seconds.
• After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
• After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
• Room temperature adjustment.
The following are added to the setting temperature specified as above.
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.