13.2. Sensible Capacity Chart
CS-E9DKEW CU-E9DKE
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.58 1.96 0.55 2.41 1.88 0.59 2.24 1.80 0.63 2.04 1.71 0.68
19.0°C 2.60 0.60
19.5°C 2.83 2.05 0.56 2.65 1.97 0.60 2.46 1.89 0.64 2.24 1.80 0.69
22.0°C 3.09 2.12 0.57 2.88 2.04 0.61 2.68 1.97 0.66 2.44 1.88 0.71
CS-E12DKEW CU-E12DKE
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 3.47 2.63 0.88 3.24 2.52 0.95 3.02 2.43 1.02 2.74 2.30 1.10
19.0°C 3.50 0.97
19.5°C 3.81 2.76 0.90 3.56 2.65 0.97 3.31 2.55 1.04 3.01 2.43 1.12
22.0°C 4.15 2.86 0.92 3.88 2.75 0.99 3.61 2.65 1.05 3.28 2.53 1.14
82
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE