Control Detection Method Protection
(i)
(ii)
Actual ion: OFF
ion feedback
signal: 5V
(i)
Actual ion OFF 2s
(i)
Case 1: During Air-Con. ON.
Air-Cond OFF with abnormal
no. H26 is activated with
timer LED is blinking
permanently.
(i)
When
becomes
(i)
Case 2: During Air-Con. OFF.
Abnormal no. H26 is
activated with timer LED is
blinking permanently for both
cases 1 & 2.
(ii)
Once
ion &
stops
(ii)
Press remote control ion
button for
a) ON: Ion LED blink
b) OFF: Ion LED OFF
(iii)
Main
reset.
(iii)
Press any remote control
button to
a) ON: Buzzer = beep beep
beep beep
b) OFF: Buzzer = beep beep
beep beep
8.1.18.2. Ionizer Operation case study
Case 1
8.2. Protection Control Features
8.2.1. Protection Control For All Operations
8.2.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of
operation.
2. This control is not applicable if the power supply is cut off and on
again or after 4-way valve deices condition.
8.2.1.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its
operation for 30 seconds.