8.2.2.2. Cooling Overload Control
i. Pipe temperature limitation/restriction
- Detects the Outdoor pipe temperature and carry out below
restriction/limitation (Limit the compressor Operation frequency)
- The compressor stop if outdoor pipe temperature exceeds 63°C
- If the compressor stops 4 times in 20 minutes, Timer LED blinking
(F95: outdoor high pressure rise protection)