– 4 –
MAC9702008C2
CS-MC90KE
Outdoor Unit
Functions
Compressor Reverse Rotation
Protection Control
Restart Control
(3 minutes)
• Once the compressor stops, the compressor
and the outdoor fan motor will not start for 3
minutes.
(Fan motor is still running if the compressor is
stopped by overload protector tripping.)
Overload Protector
Starting Current Control
(2 seconds delay)
• When both compressors are started
simultaneously, one compressor will start
immediately whereas another compressor
will start after 2 seconds.
• To protect compressor from reverse rotation
when there is a instantaneous power failure.
• Once the compressor is activated, it does not
stop for 60 secs. (Stops immediately with
remote control stop signal.)
60 secs. Forced Operation Control