– 21 –
MAC9702008C2
CS-MC90KE
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.
Operation Details
Cooling Operation Time Diagram
a
b
c
def
g
hi
j
klmnopq
rs
tuvwxyz
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
1’ 3’ 1’ 7’ 1’ 3’
4’
1.5˚C
ON
OFF
Comp.
Intake Air
Temperature
Comp.
Set Temp.
Indoor
Heat
Exchanger
Temp.
10°C
2°C
Indoor
Fan
Comp.
SLo Lo Lo Lo
ON ONOFF
stop stop stop
30"
stop
30"160"
1
40"
40"
20"
✕
.
.
.
.
2
✕
.
.
.
.
* 1 Fan Speed is Hi until the compressor stops (when the room temperature reaches
setting temperature).
* 2 Fan Speed is Me after the compressor restarts.
Operation
Stop
<Description of operation>
d – g : Time Delay Safety Control (waiting for 3 minutes)
g – h : 60 sec. Forced Operation
h – 0 : 7 min. Time Saved Control
q – t : Anti Freezing Control
<Condition>
a – h : When outdoor temperature is high
h – p : When outdoor temperature is moderate
p – w : When outdoor temperature is low