Dew prevention control will be cancel when:
- Any one of the condition above does not comply.
13.4. Outdoor Fan Residual Heat Removal Control
When the compressor stops to operate, the outdoor fan motor continue to operate for 60 seconds before stops operation.
This phenomenon is to extract the heat residual at outdoor heat exchanger.
13.5. 3-way Valve Error
This control is to protect the compressor.
Valve error is detected when:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 5 minutes).
- Indoor heat exchanger temperature at compressor start - 3°C < current indoor heat exchanger temperature for 3 minute.
Indoor suction temperature - 3°C < current heat exchanger temperature for 3 minutes.