Anti-Fog Protection
Outdoor Air Temp PE9DKE PE12DKE
0-30 a 45 58
30-90 b 40 54
90-420 c 40 54
0-30 a 45 58
30-90 b 40 54
90-420 c 35 46
0-30 a 35 46
30-90 b 35 46
90-420 c 35 46
0-30 a 35 46
30-90 b 35 46
90-420 c 35 46
800 850
960 1020Indoor Fan Speed B
2
>30
<30
Indoor Fan Speed A
Operation Time(S)
1
>30
<30
1
The indoor fan speed is higher than A but less than B.
The indoor fan speed is less than A
Overload Protection For Cooling Operation
56
53
61
58
55
55
Off
>40Hz
8Hz/45s Down
Fixed
40-51Hz(*1)
40-64Hz(*2)
The frequency for the compressor will change according
to the outdoor piping temperature.
*1 PE9DKE
*2 PE12DKE
2
31
CS-PE9DKE / CU-PE9DKE / CS-PE12DKE / CU-PE12DKE