120
INDOOR OUTDOOR TEMPERATURE (°C DB)
CU-RE28PKR
EWB EDB 20 25 30 32
%RH °C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI
51.8 14 20 7.54 5.72 1.85 7.45 5.53 2.02 7.35 5.45 2.19 7.30 5.42 2.26
54.1 16 22 7.99 5.63 1.86 7.79 5.44 2.03 7.67 5.39 2.20 7.60 5.37 2.27
50.0 17 24 8.26 5.70 1.87 8.06 5.52 2.03 7.94 5.49 2.22 7.86 5.47 2.29
50.9 18 25 8.34 5.84 1.87 8.14 5.66 2.04 8.02 5.62 2.22 7.95 5.61 2.29
47.1 19 27 8.51 6.11 1.87 8.32 5.95 2.05 8.22 5.88 2.21 8.15 5.86 2.28
50.1 22 30 9.04 5.87 1.89 8.84 5.73 2.07 8.74 5.69 2.23 8.69 5.68 2.30
51.9 24 32 9.38 5.71 1.90 9.18 5.57 2.08 9.11 5.53 2.24 9.06 5.52 2.31
INDOOR OUTDOOR TEMPERATURE (°C DB)
CU-RE28PKR
EWB EDB 35 40 46
%RH °C °C TC SHC PI TC SHC PI TC SHC PI
51.8 14 20 7.13 5.30 2.36 6.56 5.10 2.54 4.60 4.60 2.74
54.1 16 22 7.50 5.23 2.37 6.92 5.04 2.55 5.33 4.93 2.76
50.0 17 24 7.80 5.34 2.38 7.22 5.15 2.56 5.33 5.06 2.76
50.9 18 25 7.87 5.47 2.38 7.31 5.31 2.56 5.63 5.19 2.76
47.1 19 27 8.00 5.74 2.39 7.46 5.61 2.57 6.12 5.49 2.78
50.1 22 30 8.62 5.61 2.41 8.01 5.43 2.58 7.19 5.35 2.78
51.9 24 32 8.98 5.44 2.42 8.37 5.30 2.59 6.52 5.21 2.79
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)