12.10 Auto Restart Control
1 When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
2 This type of control is not applicable during ON/OFF Timer setting.
3 This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
12.11 Indication Panel
LED POWER TIMER QUIET/ECONOMY POWERFUL
Color Green Orange Orange Orange
Light ON Operation ON Timer Setting ON Quiet/Economy Mode ON Powerful Mode ON
Light OFF Operation OFF Timer Setting OFF Quiet/Economy Mode OFF Powerful Mode OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
12.12 HA Terminal (HAJEM-A)
Enable digital connection from indoor unit to external devices.
Control items:
1 Start/stop input.
2 Start/stop signal output.
Condition
1 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.
(1 pulse signal: shortage status 200 ~ 300 msec)
2 3-4 (Static output): 5V output during the unit ON. No output at OFF.