25
(EN)
• 
Use only a single wiring or stranded wiring.
•  Wiring tip arrangement.
• 
Arrange the external output wiring as well.
Connecting External Equipment
  External Input Wiring
 z Type of wiring
Use a exible wiring of 0.5 to 0.75 mm
2
.
 z Total Wire Length
100 m or less
If a longer length is needed,use a relay.
  ConnectionSpecications
COM
   1
   2
   3
  External Output Wiring
 z Exteranl output wiring specication is the same as exteranal input wiring .
 z
When outputting the operation status or alarm status, a 12 V DC external power 
source for relays is required.
• Recommended product: COSEL PBA10F-12 
• Allowable wattage: 15 W or less
 z Use the following specications for DC power wiring.
• Type of wiring: Use a exible wiring of 0.5 to 0.75 mm
2
• Arrange the power line as short as possible.
  ConnectionSpecications
Attention
   4
   6
   7
   8
+
-
⊖
⊕
⊖
⊕
   5
Status 
output
Voltage contact “a”
Static (Relay output)
•  Contact allowable 
voltage:
Max. DC12 V
•  Contact allowable 
current:
Max. 100 mA
•  Minimum application 
load:DC5 V 1 mA
Common (COM)
DC power + 
(DC 12 V +)
DC power - 
(DC 12 V -)
Alarm output 
(OUT 1)
Operation Output 
(OUT 2)
DC power 
(12 V)
Coil
Relay
Relay
Controller side External equipment side
Condition
Circuit example
Terminal
Terminal name
Condition
DC Power 
input
Non-voltage contact 
“a” Static or Pulse 
There is a polarity.
(Make sure that the 
polarity (+/-) is correct 
before connecting.)
• Power Supply  
for relays 
(Supply 12 V DC 
externally)
Controller side External equipment side
Condition
Circuit example
Terminal
Terminal name
Condition
Control 
input
Non-voltage contact “a”
Static or Pulse
•  Contact allowable 
voltage: 
DC5 V ± 10%
•  Contact allowable 
current: 
Max. 10 mA
Input 1 (IN 1)
Input 2 (IN 2)
Common (COM)
• Pulse width: 
300 msec or 
more
• 
Rated coil voltage:
 
12 V DC
Wiring
9 mm~10 mm
ENGLISH