25
(EN)
Use only a single wiring or stranded wiring.
Wiring tip arrangement.
Arrange the external output wiring as well.
Connecting External Equipment
External Input Wiring
z Type of wiring
Use a exible wiring of 0.5 to 0.75 mm
2
.
z Total Wire Length
100 m or less
If a longer length is needed,use a relay.
ConnectionSpecications
COM
1
2
3
External Output Wiring
z Exteranl output wiring specication is the same as exteranal input wiring .
z
When outputting the operation status or alarm status, a 12 V DC external power
source for relays is required.
Recommended product: COSEL PBA10F-12
Allowable wattage: 15 W or less
z Use the following specications for DC power wiring.
Type of wiring: Use a exible wiring of 0.5 to 0.75 mm
2
Arrange the power line as short as possible.
ConnectionSpecications
Attention
4
6
7
8
+
-
5
Status
output
Voltage contact “a”
Static (Relay output)
Contact allowable
voltage:
Max. DC12 V
Contact allowable
current:
Max. 100 mA
Minimum application
load:DC5 V 1 mA
Common (COM)
DC power +
(DC 12 V +)
DC power -
(DC 12 V -)
Alarm output
(OUT 1)
Operation Output
(OUT 2)
DC power
(12 V)
Coil
Relay
Relay
Controller side External equipment side
Condition
Circuit example
Terminal
Terminal name
Condition
DC Power
input
Non-voltage contact
“a” Static or Pulse
There is a polarity.
(Make sure that the
polarity (+/-) is correct
before connecting.)
Power Supply
for relays
(Supply 12 V DC
externally)
Controller side External equipment side
Condition
Circuit example
Terminal
Terminal name
Condition
Control
input
Non-voltage contact “a”
Static or Pulse
Contact allowable
voltage:
DC5 V ± 10%
Contact allowable
current:
Max. 10 mA
Input 1 (IN 1)
Input 2 (IN 2)
Common (COM)
Pulse width:
300 msec or
more
Rated coil voltage:
12 V DC
Wiring
9 mm~10 mm
ENGLISH