EasyManua.ls Logo

Panasonic CZ-RTC4A

Panasonic CZ-RTC4A
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
This function is available by attaching an optional ECONAVI sensor.
The ECONAVI sensor detects human activity and conserves energy based on the
activity level.
Overview of the ECONAVI function
High activity
• Cooling: Target temperature is the same as the set temperature.
• Heating: Target temperature is 1 °C lower than the set
temperature.
Low activity
• Cooling: Target temperature is 1 °C higher than the set
temperature.
• Heating: Target temperature is the same as the set temperature.
No one in the room No one in the room for 20 minutes
• Cooling: Target temperature is 2 °C higher than the set
temperature.
• Heating: Target temperature is 2 °C lower than the set
temperature.
No one in the room for 3 hours
• Cooling: Cooling will stop and the unit will be in fan only mode.
• Heating: Heating will stop and the unit will be in fan only mode.
* When the sensor
detects movements in
the room which have
been empty, it will
resume operation to
match with the activity
level.
Note
Even when target temperature is changed through the ECONAVI function, the set
temperature shown in the remote controller does not change.
Even when Cooling/Heating is changed to Fan through the ECONAVI function, the
operation mode shown in the remote controller will still be Cooling/Heating.
It is possible to choose from the following options for the operation to be
performed after a lapse of 3 hours since the room has been empty.
Operates in the Fan mode only.
Stops and resumes operations after human movements are detected.
Stops and will not resume operations even after human movements are
detected.
Continues to operate in the current mode.
If you need to do so, please contact the dealer.
ECONAVI Function