EasyManuals Logo

Panasonic EAIRC-MJ Series Service Manual

Panasonic EAIRC-MJ Series
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
1 - 14
1
Mini VRF SYSTEM
Control Functions
(1)
*
(2)
Thermostat OFF
Thermostat ON
20 pulses
20 pulses
20 pulses
Cooling
Outdoor unit stopped
Fan
Stop
Outdoor unit operating
MOV position (pulses)
20 pulses
20 pulses
20 pulses
60 – 480 pulses
Performs SH control
65 – 80 pulses
65 – 80 pulses
65 – 80 pulses
60 – 480 pulses
Thermostat ON
MOV position (pulses)
Stop
Fan
Heat
Thermostat OFF
accumulation
Control to prevent refrigerant
Control to prevent refrigerant
accumulation
Control to prevent refrigerant
accumulation
Performs SC distribution control
85 pulses
85 pulses
85 pulses
* The target value for SC control is 5 – 20°C for the temperature difference between the pressure
sensor temperature and E1, depending on the operating conditions.
INDOOR UNIT
8-1. During Normal Control
During Cooling mode operation
Outdoor unit operating Outdoor unit stopped
The target value for SH control is 2 – 6°C for the temperature difference between E3 and E1,
depending on the operating conditions.
However, the SH target value may increase if the required level decreases. In this case, because the
electronic control valve position moves toward the closed side, you should not assume that there is
insufficient gas.
During Heating mode operation
8. Indoor Unit Electronic Control Valve (Motor Valve) Control
SM830195-04_Mini VRF SYS.indb 14 15/03/10 17:47:35

Table of Contents

Other manuals for Panasonic EAIRC-MJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic EAIRC-MJ Series and is the answer not in the manual?

Panasonic EAIRC-MJ Series Specifications

General IconGeneral
BrandPanasonic
ModelEAIRC-MJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals